How much material can be removed?

So, just how much material can be removed from metal studs without compromising their integrity?

The Cold-Formed Steel Engineers Institute has an answer inย CFSEI Tech Note G500-11ย (โ€œGuidelines for Inspecting Cold-Formed Steel Structural Framing in Low Rise Buildingsโ€). Under section 1.0 Materials, paragraph 1.3 Web Holes, CFSEI Tech Note G500 says this:

  • โ€œThe size of a web hole should not be larger than one-half the web depth, or 2-ยฝโ€ maximum in the web direction and not more than 4-ยฝโ€ long in the member direction.โ€

Theย Code Compliance Research Report, CCRR-0224, from Intertek says the same in paragraph 3.2:

  • โ€œWeb punch-out widths shall not exceed 2.5 inches, or half of the member depth. Web punch-out length shall not exceed 4.5 inches.โ€

The ICC Evaluation Service, a subsidiary of the International Code Council, recommends a smaller hole limit:

Pat Ford, Steel Framing Industry Association (SFIA) technical director, says that a few limited holes within CFS studs may be safely executed in the field. But, those cut studs will still need a thorough engineering review, he says. Some may need to be replaced.

Use factory punch-outs on CFS studs

The wise course is to use factory engineered punch-outs in CFS studs, rather than cut or notch studs in the field.

Metal framing contractors donโ€™t generally notch or bore holes into CFS studs anyway. They install studs as they come from the factory. And many stud products have punch-outs to accommodate bridging members, as well as electrical, plumbing and HVAC elements.

Factory produced punch-outs can prevent random notching or boring that could otherwise compromise the integrity of the stud.

 

Article cited fromย www.buildsteel.org